2 MW Liquid-Cooled Load Bank

Simulate IT heat loads during commissioning, integrated system testing and performance validation. Four independently controlled 500 kW heating clusters provide precise regulation.

2 MW liquid-cooled load bank

As Seen with Microsoft

See how Liquidpulse load banks support the infrastructure behind next-generation data centers.

Check out the interview with Microsoft where Liquidpulse load banks are featured at the Fairwater 2 Data Center in Atlanta. 

Watch on YouTube

Key Features

Independent heating clusters

Four 500 kW clusters with independent IGBT load control.

Modular operation

Units support individual or synchronized control.

Monitoring and alarms

PLC with 10-inch touchscreen HMI and field-adjustable alarms.

Technical Specifications:

Model

LP-AC400V-2MW

Heating capacity

2 MW at 415 V; 2.4 MW at 480 V

Test media

Water or PG25

Load steps

5 kW

Flow rate

800 gpm nominal; 1,600 gpm maximum

Maximum allowable working pressure

150 psi

Input power

400–480 VAC, 3 phase, 60 Hz

Electrical protection

Four circuit breakers for short-circuit protection; built-in 24 VDC control power

Controls

PLC with 10-inch touchscreen HMI

Communications

Modbus RTU, Modbus TCP/IP, SNMP; two RJ-45 ports

Monitoring

Pressure, flow, temperature, power, ambient temperature and relative humidity

Piping

304 stainless steel

Base and dimensions

Built-in casters; 62 in W × 79 in H × 39 in D

Electrical panel

UL 508A