2 MW Liquid-Cooled Load Bank
Simulate IT heat loads during commissioning, integrated system testing and performance validation. Four independently controlled 500 kW heating clusters provide precise regulation.
As Seen with Microsoft
See how Liquidpulse load banks support the infrastructure behind next-generation data centers.
Check out the interview with Microsoft where Liquidpulse load banks are featured at the Fairwater 2 Data Center in Atlanta.
Key Features
Independent heating clusters
Modular operation
Monitoring and alarms
Technical Specifications:
Model
LP-AC400V-2MW
Heating capacity
2 MW at 415 V; 2.4 MW at 480 V
Test media
Water or PG25
Load steps
5 kW
Flow rate
800 gpm nominal; 1,600 gpm maximum
Maximum allowable working pressure
150 psi
Input power
400–480 VAC, 3 phase, 60 Hz
Electrical protection
Four circuit breakers for short-circuit protection; built-in 24 VDC control power
Controls
PLC with 10-inch touchscreen HMI
Communications
Modbus RTU, Modbus TCP/IP, SNMP; two RJ-45 ports
Monitoring
Pressure, flow, temperature, power, ambient temperature and relative humidity
Piping
304 stainless steel
Base and dimensions
Built-in casters; 62 in W × 79 in H × 39 in D
Electrical panel
UL 508A