500 kW Liquid-Cooled Load Bank

Simulate IT heat loads during data center cooling system commissioning, stress testing and integrated system testing. The modular units can run independently or together across a range of heating capacities.

500 kW liquid-cooled load bank

As Seen with Microsoft

See how Liquidpulse load banks support the infrastructure behind next-generation data centers.

Check out the interview with Microsoft where Liquidpulse load banks are featured at the Fairwater 2 Data Center in Atlanta. 

Watch on YouTube

Key Features

Stainless steel construction

304 stainless steel and high-level cleaning before shipment.

Cluster control

An optional cluster controller lets teams monitor and operate up to 120 units from one location.

Load and system monitoring

PLC control, a 10-inch touchscreen HMI and field-adjustable alarms and faults.

Technical Specifications:

Model

LP-AC400V-500kW

Heating capacity

500 kW at 415 V; 535 kW at 480 V

Test media

Water or PG25

Temperature rise (PG25)

10 °C at 200 gpm

Load steps

25/50 kW

Maximum flow rate

400 gpm

Maximum allowable working pressure

150 psi

Pressure drop

< 2 psi at 200 gpm

Input power

400–480 VAC, 3 phase, 60 Hz

Current draw

697 A at 415 VAC

Electrical protection

Circuit breaker short-circuit protection; built-in 24 VDC control power

Controls

PLC with 10-inch touchscreen HMI

Communications

Modbus RTU, Modbus TCP/IP, SNMP; two RJ-45 ports and one RS-485 port

Monitoring

Pressure, flow, temperature, power, ambient temperature and relative humidity

Piping and process connections

304 stainless steel; 4-inch process connections

Base and dimensions

Built-in casters; 62 in W × 79 in H × 39 in D

Certifications

UL 508A electrical panel; ASME U pressure vessel