500 kW Liquid-Cooled Load Bank
Simulate IT heat loads during data center cooling system commissioning, stress testing and integrated system testing. The modular units can run independently or together across a range of heating capacities.
As Seen with Microsoft
See how Liquidpulse load banks support the infrastructure behind next-generation data centers.
Check out the interview with Microsoft where Liquidpulse load banks are featured at the Fairwater 2 Data Center in Atlanta.
Key Features
Stainless steel construction
Cluster control
Load and system monitoring
Technical Specifications:
Model
LP-AC400V-500kW
Heating capacity
500 kW at 415 V; 535 kW at 480 V
Test media
Water or PG25
Temperature rise (PG25)
10 °C at 200 gpm
Load steps
25/50 kW
Maximum flow rate
400 gpm
Maximum allowable working pressure
150 psi
Pressure drop
< 2 psi at 200 gpm
Input power
400–480 VAC, 3 phase, 60 Hz
Current draw
697 A at 415 VAC
Electrical protection
Circuit breaker short-circuit protection; built-in 24 VDC control power
Controls
PLC with 10-inch touchscreen HMI
Communications
Modbus RTU, Modbus TCP/IP, SNMP; two RJ-45 ports and one RS-485 port
Monitoring
Pressure, flow, temperature, power, ambient temperature and relative humidity
Piping and process connections
304 stainless steel; 4-inch process connections
Base and dimensions
Built-in casters; 62 in W × 79 in H × 39 in D
Certifications
UL 508A electrical panel; ASME U pressure vessel
Literature and Documentation: