HRT-1400 CDU

A 1,400 kW coolant distribution unit for systems using softened water on the primary side and PG25 on the secondary side.

HRT-1400 coolant distribution unit

Key Features

1,400 kW nominal capacity

Rated at a 4 °C approach temperature.

Redundant control power

Dual AC and dual DC power supplies.

Secondary filtration

50 µm filtration and up to 475 gpm on the secondary side.

Technical Specifications:

Nominal cooling capacity

1,400 kW

Approach temperature

4 °C

System design pressure

72.5 psi

Available pressure drop

26 psi

Primary side

Softened water; 317 gpm rated; 4.5-inch tri-clamp

Secondary side

PG25; 317 gpm rated and 475 gpm maximum; 50 µm filtration; 4-inch tri-clamp

Piping

304 stainless steel

Base

Metal frame with casters and forklift slots

Dimensions

900 W × 1200 D × 2200 H mm

Control and redundancy

Temperature, pressure and flow control; dual AC and dual DC power supplies

Interface and communications

10-inch touchscreen HMI; Modbus TCP/IP; RJ-45 and RS-485

Monitoring

Pressure, flow, fluid temperature, relative humidity and temperature, power

Certification

UL Listed

Literature and Documentation:

CONTACT US